Production on the basis of the specification: TU 3414-024-52889537-07.
Reverification interval – 8 years.
Service life – at least 30 years.
Guaranteed service life – 5 years.
Registered in the Measuring Instrument State Registers of the Russian Federation, Republic of Belarus, Ukraine, Republic of Kazakhstan.
Certified by Rosseti (PAO)
An example of identification of TLO-24 current transformer in M1 dimension:
ТLО-24 М1A – 0,2/10Р-10/15-600/5 NЗ 40 kА б, TU 3414-024-52889537-07
М1 |
- transformer dimension |
A |
- secondary terminals on the transformer body are located at the end surface |
0,2 |
- accuracy class of the measuring secondary winding |
10Р |
- accuracy class of the protective secondary winding |
10 |
- rated secondary burden of the measuring secondary winding, V·А |
15 |
- rated secondary burden of the protective secondary winding, V·А |
600 |
- rated primary current , А |
5 |
- rated secondary current , А |
N |
- climatic modification |
3 |
- placement category |
40 |
- short-time (one second) thermal current, kА |
б |
- insulation level |
Наименование | Значение |
---|---|
Rated voltage, kV | 20,24 |
Maximum operating voltage, kV | 26,5 |
Rated primary current, А | 5; 7,5; 10; 11; 12; 13; 14; 16; 15; 18; 20; 22; 25; 27,5; 30; 32,5; 35; 37,5; 40; 50; 55; 60; 65; 70; 75; 80; 90; 100; 150; 200; 250; 300; 350; 400; 500; 550; 600; 650; 700; 750; 800; 900; 1000; 1050; 1100; 1150; 1200; 1250; 1300; 1400; 1500; 1550; 1600; 1650; 1700; 1750; 1800; 1900; 2000; 2100; 2200; 2250; 2300; 2500; 2550; 2600; 2650; 2700; 2750; 2800; 2900; 3000 |
Rated secondary current, А | 1; 5 |
Rated frequency, Hz | 50; 60 |
Number of secondary windings | up to 5 |
Rated secondary burdens with cosφ=0.8 | |
measuring windings, V·А | from 1 up to 50 |
protective winding, V·А | from 1 up to 50 |
Rated accuracy class: | |
measuring windings | 0,2S; 0,2; 0,5S; 0,5; 1; 3 |
protective windings | 5Р or 10Р |
Accuracy limit factor Krated of secondary protective winding | from 2 up to 30 |
Rated instrument security factor FSrated of measuring winding | from 3 up to 30 |
Short-time (one second) thermal current kА, at rated primary current | |
5-20 А | 2,5; 5 |
30-50 А | 5; 10; 20 |
75-100 А | 10; 20; 31,5; 40 |
150 А | 15; 20; 31,5; 40 |
200 А | 20; 31,5; 40-60 |
300 А | 31,5; 40-100 |
400-3000 А | 40-100 |
Dynamic current kА, at rated primary current | |
5-20 А | 6,25; 12,8 |
30-50 А | 12,8; 26; 52 |
75-100 А | 26; 52; 81; 100 |
150 А | 39; 52; 81; 100 |
200 А | 52; 81; 100-150 |
300 А | 81; 100-250 |
400-3000 А | 100-250 |
Weight, kg, not more | from 30 up to 150 |
Overall dimensions, (LxWxH), mm | 460х400х426 |
*Для трансформаторов с расширенным диапазоном первичного тока погрешности при токе 150 % и 200 % номинального первичного тока не превышают пределы допускаемых погрешностей для 120 % номинального первичного тока.
**Для классов точности TPX, TPY, TPZ по ГОСТ Р МЭК 61869-2 значения номинальной вторичной нагрузки S2ном пересчитываются по формуле, В·А:
где Rb– номинальное values for parameters резистивной нагрузки по ГОСТ Р МЭК 61869-2;
I2ном – номинальный вторичный ток, А.