Current transformer TV-EK M3

The main specific features of this design

TV-EK М3 transformers are designed to equip power transformers already being in operation. The high-voltage bushing of the power transformer is the primary winding of these transformers. The insulation is represented by the transformer body made of compound and by insulation of the end product primary winding.  Secondary terminals are located on the transformer body are terminated to the junction box.

Полезная информация
Operation Manual See Download
Product passport See Download
Certificates See Download
Data Sheet form See Download
Наименование Значение
Метрологические parameters
Номинальное напряжение, кВ 0,66; 3; 6; 10; 15; 20; 24; 27; 35; 110; 150; 220; 330; 500; 750
Наибольшее рабочее напряжение, кВ 0,72; 3,6; 7,2; 12; 17,5; 24; 26,5; 30; 40; 126; 172; 252; 363; 525; 787
Номинальный первичный ток, А от 50 до 45000
Номинальный вторичный ток, А 1; 2; 2,5; 5
Номинальная частота, Гц 50; 60
Номинальная вторичная нагрузка с индуктивно-активным коэффициентом мощности cosϕ2=0,8, ВА от 1 до 150
Классы точности вторичных обмоток для измерений и учета по ГОСТ 7746-2015 0,2S; 0,2; 0,5S; 0,5; 1; 3; 5; 10
Классы точности вторичных обмоток для защиты: - по ГОСТ 7746-2015 - по ГОСТ Р МЭК 61869-2-2015 5Р; 10Р 5PR; 10PR; ТРY; ТРZ; PX; ТРХ
Номинальный коэффициент безопасности KБном вторичных обмоток для измерения и учета от 3 до 50
Номинальная предельная кратность Kном вторичных обмоток для защиты от 2 до 300
Технические parameters
Масса, кг не более от 1 до 1500
Габаритные размеры (Dнар х dвнутр х Н) max. 1400х1200х500

 

Габаритные размеры